Ductwork CFM Calculator

This answers the three airflow questions a duct layout runs into. The first turns a sensible heating or cooling load into CFM with the sensible heat equation, corrected for site elevation because thinner air carries less heat per cubic foot. The second takes equipment capacity in tons or BTU per hour and returns total supply airflow at a chosen CFM per ton, with the acceptable band around it. The third splits that total between rooms by floor area, or by a load share you already have, and counts the supply registers. Sizing the duct itself is a different equation and a different page.

Calculator Type
Load, Temperature and Airflow In
Elevation In

The sensible heat equation. Give the load the air has to carry and the temperature difference between the supply air and the room.

Sensible only. The latent part of a cooling load is removed by the coil, not carried by the airflow.
Around 18 to 22 F across a cooling coil, which is 10 to 12 C, and 40 to 70 F on a gas furnace, which is 22 to 39 C. This is a difference between two temperatures, so it converts at 1.8 with no 32 degree offset.
In whichever unit you picked above. The density correction is written in feet, so metres are converted first.
Widget
Capacity Entered In
The airflow follows the capacity, because the two really are one convention: "CFM per ton" is the American rule and "litres per second per kilowatt" is the same rule everywhere else. There is no such quote as CFM per kilowatt.

Total supply airflow for a piece of equipment, at a chosen airflow per ton.

Left blank it is 400 CFM per ton, which is 53.7 litres per second per kilowatt. A dry climate is often run at 450 (60.4), a humid one at 350 (47.0).
Left blank it is 350 CFM per ton, which is 47.0 litres per second per kilowatt.
Left blank it is 450 CFM per ton, which is 60.4 litres per second per kilowatt.
Widget
Airflow In
Floor Areas In
Both areas are read in the same unit. The split is a ratio, so either unit gives the same airflow.

A room takes its share of the system airflow. By floor area, or by a load share you already have.

Leave at 0 to split by floor area. Give a figure here and it is used instead, which is the right answer for a room whose load is nothing like its floor area.
What one register and its branch will actually carry. Common residential registers are run at 75 to 150 CFM, which is 35 to 71 litres per second. Left blank it is 100 CFM, which is 47.2 litres per second.