Conduit Fill Calculator

A conduit fill calculator that follows NEC Chapter 9, applying the Table 1 limits of 53 percent for one conductor, 31 percent for two and 40 percent for three or more to the Table 4 conduit areas. Pick the conduit type, the trade size and a THHN or THWN-2 conductor size, and it either checks a pull you have already planned or tells you how many conductors of that size fit. The conductor areas come from the Table 5 THHN/THWN-2 column, so another insulation has a different area, and a mix of sizes has to be added up by hand. Verify the result against the code edition your jurisdiction has adopted, because the local inspector's reading governs the job.

Calculator Type
Count every conductor in the raceway, including the equipment grounding conductor.