Heat Pump Size Calculator

A heat pump loses output as it gets colder while the house needs more, so the two cross at a temperature called the balance point. Enter the design heating load and design temperature along with the unit's rated capacity at 47 F and 17 F, and optionally at 5 F, and this returns where those two lines meet, how much capacity survives at the design temperature, and how many kilowatts of backup heat the shortfall leaves. A second mode works backwards, giving the 47 F rating needed to hold a balance point you choose and showing how far that size overshoots the cooling load. The load itself should come from a Manual J calculation, and capacity between the rated points is taken as a straight line rather than from the manufacturer's own table.

Calculator Type
The heat the building loses at the outdoor design temperature. A Manual J load calculation is where this comes from.
The 99% winter design temperature for your location, not the record low.
From the manufacturer submittal or the AHRI certificate, at maximum compressor speed.
Leave blank and the 47 to 17 line is extended downwards, which flatters most units below 17 F.
Widget
The temperature below which you accept backup heat. Set it to the design temperature to cover the whole season on the compressor.
Around 60% for a conventional unit, 80% or better for a cold-climate inverter model.