Superheat Calculator

This works out the superheat and the subcooling on a refrigeration or air conditioning system from readings you have already taken. Enter the saturation temperature that matches the gauge pressure, taken from the pressure-temperature chart for the refrigerant in the machine, and the temperature of the suction or liquid line, and it returns the difference in Fahrenheit or Celsius degrees with the range that reading normally falls in. A third action gives the target superheat for a piston or capillary tube system from the indoor wet bulb and outdoor dry bulb. No refrigerant table is built in, because the saturation temperature depends on which blend is actually in the system and whether you want its bubble point or its dew point.

Calculator Type
Temperature Scale
Both temperatures must be in the same scale.
Read the low side pressure on the gauge, then convert it with the pressure-temperature chart for the refrigerant in the system. For a zeotropic blend use the dew point column, because that is the state at the evaporator outlet.
Taken with a clamp or strapped probe on the bare copper, insulated from the air, at the same point the pressure was read.
Widget
Measured in the return air stream with a sling psychrometer or a wet bulb probe. 67 degrees F is the rating condition, roughly 80 degrees F dry bulb at 50 percent relative humidity.
Ambient air entering the condenser, in the shade, not the temperature off the top of the unit.
Leave at zero if you only want the target. A genuine reading of zero is a flooding evaporator and belongs in the superheat action above, not here.
Widget
Temperature Scale
Both temperatures must be in the same scale.
High side gauge pressure put through the pressure-temperature chart. For a zeotropic blend use the bubble point column, because that is the state of the liquid leaving the condenser.
On the bare copper of the liquid line near the service valve, insulated from the air.
Widget